SIDNs
S00043Velocitypolarityparameter
Theparametercanbeusedtoinvertthepolarityofthevelocitydatainspecialapplications.
Attributes
Name Value
Format binary
Datalength 16
Decimalpoint 0
Minvalue 0
Maxvalue #x000F
Defaultvalue
Unit
ChangeableinEtherCATstate PreOp
Cyclictransfer No
Deviceparameter No
Relatedtointerfacerevision No
Thepolaritiesareswitchedattheinputandoutputoftheclosedcontrolloopandthereforedonotaffectthe
closedcontrolloopsinthedrive.Themotorshaftrotatesinaclockwisedirection(viewedfromthefrontonto
themotorshaft),ifthereisapositivevelocitysetvaluedifferenceandthereisnoinversion.
Bitpattern:
Bit Meaning
0 Velocitycommandvalue
Velocitycommandvalue
0=polaritynotinverted
1=polarityinverted
1 Additivevelocitycommandvalue
Additivevelocitycommandvalue
0=polaritynotinverted
1=polarityinverted
2 Velocityfeedbackvalue1
Velocityfeedbackvalue1
0=polaritynotinverted
1=polarityinverted
3 Velocityfeedbackvalue2
Velocityfeedbackvalue2
0=polaritynotinverted
1=polarityinverted
415 Reserved
AX5000IDNDescriptions46 Version3.1