SIDNs
S00201Motorwarningtemperature
Ifthetemperatureinthemotorexceedsthisvalue,thedrivesetschangebit1ofS00012,andawarningis
generated.
Attributes
Name Value
Format udec
Datalength 16
Decimalpoint 1
Minvalue 40.0
Maxvalue 150.0
Defaultvalue 80.0
Unit °C
ChangeableinEtherCATstate PreOp
Cyclictransfer No
Deviceparameter No
Relatedtointerfacerevision No
Note
IDNsinvolved
S‐0‐0012 [}14]
AX5000IDNDescriptions 135Version3.1