Distributed Clocks (0x0900:0x09FF)
II-72 Slave Controller – Register Description
Table 121: Register Latch0 Status (0x09AE)
Event Latch0 positive edge.
0: Positive edge not detected or
continuous mode
1: Positive edge detected in single event
mode only.
Flag cleared by reading out Latch0 Time
Positive Edge.
Event Latch0 negative edge.
0: Negative edge not detected or
continuous mode
1: Negative edge detected in single event
mode only.
Flag cleared by reading out Latch0 Time
Negative Edge.
Table 122: Register Latch1 Status (0x09AF)
Event Latch1 positive edge.
0: Positive edge not detected or
continuous mode
1: Positive edge detected in single event
mode only.
Flag cleared by reading out Latch1 Time
Positive Edge.
Event Latch1 negative edge.
0: Negative edge not detected or
continuous mode
1: Negative edge detected in single event
mode only.
Flag cleared by reading out Latch1 Time
Negative Edge.