Commissioning
bValid:IfthisoutputissetthedataintheST_UPSStatusstructurearevalid(noerroroccursatthelastread
cycle).
bError:Thisoutputissetifanerroroccursbyexecutionofthefunction.
nErrId:SuppliestheAdserrornumberoracommandspecificerrorcode(table)whenbErroroutputisset.
stStatus:StructurewiththestatusinformationofUPS.
Errorcodes Errordescription
0x0000 noerror
0x8001 UPSconfigurationerror.PerhapstheUPSisnot
configuredcorrectly,ornoUPSisconfigured.
0x8002 Communicationerror.ThecommunicationtotheUPS
hasbeeninterrupted.
0x8003 Errorbyreadingthestatusdata.
Note:
NotallUPSdevicesareabletodeliverstatusinfomation.Somedevicescan´tdelivere.gBatteryLifeTimeor
BatteryReplaceStatus.
ExampleforacallinFBD
OnlinedatawithstatusinformationofUPS:
CX210009x4 69Version1.1