Commissioning
Name Type Description Defaultvalue
othervaluesarenotpermissible;
TurnUPSOffWait REG_DWORD Maximumdelaytimeinsecondsforswitching
offtheUPSoutputvoltageafterinitiatingthe
Windowsshutdown.Thepermissiblevalues
candifferfrommodeltomodel(dependingon
hardware).
180
BatteryReplaceNoti
fyEnable
REG_DWORD Activates/deactivatestheloggingofthebattery
changeserviceintervalwarningsinthe
Windowseventlog:UPSsoftwarev3.0.0.8
andhigher.
0
BatteryReplaceNoti
fyWait
REG_DWORD Delaytimeinmonthsforthefirstbattery
changewarning.Thiselementcanadopta
valueofbetween0and480months.Other
valuesarenotpermissible.Implementedinthe
UPSsoftwarev3.0.0.8andhigher.
60
AdvancedSettings
KEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\UPS
Name Type Description Defaultvalue
FirstMessageDelay REG_DWORD Delaytimeinsecondsforthefirstpower
failmessagetotheuser
5
MessageInterval REG_DWORD Delaytimeinsecondsforfurtherpower
failmessagestotheuser.
20
CX210009x4 67Version1.1