Beckhoff CX2100­09x4 Manual de usuario Pagina 51

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 87
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 50
Commissioning
Setting/command Area Defaultvalue Description
Batterytype 0..99 1 OnlyspecificfortheBeckhoffP24VxxxxUPS
fromfirmwareversion>=24.1.Iandrequired,
forexample,inordertocalculatetheremaining
batterycapacityinbatterymode.
Nominalbattery
capacity
0..99900[mAh] 3400 OnlyspecificfortheBeckhoffP24VxxxxUPS
fromfirmwareversion>=24.1.Iandrequired,
forexample,inordertocalculatetheremaining
batterycapacityinbatterymode.
Batteryinternal
resistance
0999[mOhm] 120 OnlyspecificfortheBeckhoffP24VxxxxUPS
fromfirmwareversion>=24.1.Iandrequired,
forexample,inordertocalculatetheremaining
batterycapacityinbatterymode.
Batterychange
intervalservice
0480
[months]
60(5years)
andcheckbox
notchecked
OnlyfortheBeckhoffP24VxxxxUPSfromUPS
softwarev3.0.0.8orhigher.Anintervalservice
canbeconfiguredforthisonwhoseexpirybattery
changewarningsarewrittenintotheWindows
eventlog.Usethecheckboxtoactivateor
deactivatethefunction.Thenumberofmonths
beforethefirstwarningmustadditionallybe
configuredintheEditfield.Thefunctionisonly
availableifthedateofthelastbatterychangeand
theWindowssystemtime(inthetaskbar)have
alsobeencorrectlyset/configured.TheUPS
servicecomparesthedateofthelastbattery
change+intervalservicewiththesystemdate.If
thesystemdateisexceeded,awarningiswritten
intotheeventlog.Thewarningdoesnotprovide
anyinformationabouttheactualbatterystateand
canonlybeusedasaremindertocheckthe
batterystate/age.
Lastservice:01.01.11* Displaysthedateofthelastbatterychange(last
servicewasonJanuary1,2011).
Nextservice:
01.01.16*
Showstheprospectivedateofthenextbattery
change(nextserviceisdueonJanuary1,2016).
Resetintervalservice
message…
OnlyfortheBeckhoffP24VxxxxandsomeAPC
devices.Updatesthedateofthelastbattery
changeandresetstheintervalservicemessage.
ThedateisstoredintheUPS'sEEPROM,and
canbeexaminedintheUPS information [}49]
dialog.
setto:25.05.12* Displaysthedatewhichissuggestedwhen
resettingtheservicemessage.Thelastbattery
change/serviceisupdatedtothisdate(thecurrent
dateisMay25,2012).
Firmwareupdate... OnlyfortheBeckhoffP24Vxxxxfromfirmware
version:>=21.1.I.Startsafirmwareupdate.Only
startsafirmwareupdateifyouactuallyhavea
suitablenewfirmwarefile.
Selftest OnlyfortheBeckhoffP24VxxxxandsomeAPC
devices.Executesaselftestanddisplaysthe
result:
"OK"Testsuccessful,thebatteryisOK;
"BT"failedduetoinsufficientbattery
capacityornobatteryispresent\connected
atall;
"NG"Failedasaresultofoverload;
"NA"Testfunctiondoesnotexist;
CX210009x4 51Version1.1
Vista de pagina 50
1 2 ... 46 47 48 49 50 51 52 53 54 55 56 ... 86 87

Comentarios a estos manuales

Sin comentarios