Commissioning
4.2 1SecondsUPS
4.2.1 Overview
ThelibraryTcSUPS_CX9020_U900.libincludesfunctionsandfunctionblocksrequiredforcontrollingthe
onesecondUPS.
Functionblocks
Name Description
FB_S_UPS_CX9020_U900 BlockforcontrollingtheonesecondUPS
FB_NT_QuickShutdown InternalblockforQuickShutdown,usedbythe
FB_S_UPS.
Functions
Name Description
F_GetVersionTcSUPS_CX9020_U900 ThisfunctioncanbeusedtoreadPLClibraryversion
information.
Component Version
TwinCATonthedevelopmentPCandonthecontrol
system
TwinCAT2.11R3Build2047orhigher
4.2.1.1 FUNCTION_BLOCKFB_S_UPS_CX9020_U900
ThefunctionblockFB_S_UPS_CX9020_U900canbeusedonCXdeviceswithonesecondUPStocontrol
theonesecondUPSfromthePLC.Thisallowsthepersistentdatatobesavedandaquickshutdowntobe
performedintheeventofapowerfailure.IfpossiblethedefaultvaluesoftheINPUTsofthe
FB_S_UPS_CX9020_U900shouldberetained.
Attention
Lossofdata
ThesecondsUPScanbeusedonlyforafewsecondsintheeventofapowerfailureinor
der,tosavepersistentdata.Thedatamustbesavedinthefast“persistentmode”
“SPDM_2PASS”,eventhoughthiscanleadtorealtimeviolations.Sufficientroutermemory
mustbeconfiguredforthestorageofthepersistentdata!
ThesecondUPSdoesnothavesufficientcapacityforbridgingpowerfailures.OnlytheCFastcardcanbe
usedfordatastorage,inviewofthefactthattheUPScapacityisinadequateforoperatingaharddisk.
AQuickShutdownisperformedautomaticallyintheeSUPS_WrPersistData_Shutdownmode(standard
setting)afterthestorageofthepersistentdata.
IneSUPS_WrPersistData_NoShutdownmodeonlythepersistentdataarestored.NoQuickShutdownis
executed.
CX902032 Version1.1