Beckhoff CX9020 Manual de usuario Pagina 20

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 19
Mountingandwiring
Theterminalsareimplementedinspringforcetechnology.Connectthecablesasfollows:
1. Openaspringloadedterminalbyslightlypushingwithascrewdriverorarodintothesquareopening
abovetheterminal.
2. Thewirecannowbeinsertedintotheroundterminalopeningwithoutanyforce.
3. Theterminalclosesautomaticallywhenthepressureisreleased,holdingthewiresecurelyand
permanently.
Wiresizewidth 0.5...2.5mm
2
AWG20..AWG14
Wirestrippinglength 8...9mm 0.33inch
LED
Ifthepowersupplyunitisconnectedcorrectlyandthepowersupplyisswitchedon,thetwoupperLEDsin
theterminalprismaregreen.TheleftLED(Us)indicatestheCPUsupply.TherightLED(Up)indicatesthe
terminalsupply.TheotherLEDsindicatetheTerminalBusstatus.AdetaileddescriptionoftheLEDscanbe
foundinsection"LEDtroubleshooting".
ULrequirements
DANGER
ComplianceoftheULrequirements
ForthecomplianceoftheULrequirementstheCXControllersshouldonlybesuppliedbya
24VDCsupplyvoltage,suppliedbyanisolatingsourceandprotectedbymeansofafuse
(inaccordancewithUL248),ratedmaximum4Amp.bya24VDCpowersource,thathasto
satisfyNECclass2.ANECclass2powersupplyshallnotbeconnectedinseriesorparal
lelwithanother(class2)powersource!ThisULrequirementsarevalidforallsupplyvolt
agesoftheCXControllers!
DANGER
ComplianceoftheULrequirements
TomeettheULrequirements,theCXControllersmustnotbeconnectedtounlimited
powersources!
CX902020 Version1.1
Vista de pagina 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 47 48

Comentarios a estos manuales

Sin comentarios