Beckhoff CX9020 Manual de usuario Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
Errorhandlinganddiagnostics
Kbusstate
TheKbusstatusissavedinthestatebyte(seefig.Kbusinterface“1”).Ifthevalueis0theKbusis
operatingsynchronouslyandwithouterrors.Ifthevalueis<>”0”theremaybeafault,oritmayonlybean
indicationthattheKbuscycleislongerthanthetask,inwhichcaseitwouldnolongerbysynchronouswith
thetask.Thetasktimeshouldbefasterthan100ms.Werecommendatasktimeoflessthan50ms.TheK
busupdatetimetypicallyliesbetweenoneandfivems.
Bit0=KBuserror
Bit1=terminalconfigurationhaschangedsincethestart
Bit2=processimagelengthsdonotmatch
Bit8=novalidinputs(yet)
Bit9=Kbusinputupdatenotyetcomplete
Bit10=Kbusoutputupdatenotyetcomplete
Bit11=watchdog
Bit15=acyclicKbusfunctionactive(e.g.Kbusreset)
IfthereisaKbuserror,thiscanberesetviatheIOF_DeviceResetfunctionblock(intheTcIoFunctions.lib).
CX9020 41Version1.1
Vista de pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 47 48

Comentarios a estos manuales

Sin comentarios