Mountingandwiring
Attention
Avoiddamage!
Donotforcethemoduleorapplyexcessivepressure!
Installationposition
Attention
Complywiththepermittedinstallationpositionandminimumdistances!
ThemaximumambienttemperatureforCPUmodulesmountedonaDINrailis60°C.The
orientationinwhichthedeviceisfittedmustbeselectedinsuchawaythatcoolingaircan
flowverticallythroughtheventilationholes.Theimagesbelowshowthepermittedandtwo
incorrectinstallationpositions.Mountingmustprovideaclearanceof30mmbothabove
andbelowaCX20x0devicecombinationtoensureadequateventilationofthebaseCPU
moduleandthepowersupplyunit.
Correctinstallationposition
ThehighperformanceandthecompactdesignoftheCX20x0systemsmayresultinincreasedheat
generation.Theheatisdissipatedviaapassiveventilationsystem.Thissystemrequirestheunittobe
mountedcorrectly.Ventilationopeningsarelocatedatthetopandbottomofthehousing.Thesystem
thereforehastobeinstalledhorizontally.Thisensuresoptimumairflow.
CX210000x4 31Version1.0