Beckhoff M2400 Manual de usuario Pagina 6

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 15
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 5
M2400 Analog Output Beckhoff I/O-System
page 6 of 6 Version : 2.1 Date : 11.06.2002
3. Technical Data
Analog Outputs
max. 4
Analog Specifications
U
out
= ±10 V , I
out
= 0 to 20 mA
Resolution : 12 Bit
Error, linearity
+/- 1 LSB
Rise time
10 us von -10V ==> +10V
Inputs / Outputs
16, can be configured for each port;
LED shows state of all inputs / outputs
input switching vcoltages
0 - 8V = LOW
15 - 24V = HIGH
input delay
0,7 ms RC network
6,8 ms input latch
Input Specifications
24 V DC, 10 mA, digital filter
Output Specifications
24 V DC, max. 500 mA, short circuit proof
Output check
watchdog system (100ms)
Connections
a) can be connected for digital I/O ; +,-,signal
b) for analog output; signal,-,potential free contact, 1
permission input 24 VDC for each channel
Data Connection
fibre optic II/O system
Transmission Rate
2,5 MBaud, 25 µs for 32 Bit
Supply Voltage
24 V DC (± 10%)
Input Current
0,1 A (without load and input currents)
Cartridge
Aluminium profile cartridge, can be installed to
cartridge carrier according to DIN EN 50022, 50035
Size (B * W * D)
270 * 76 * 68 mm
Weight
about 1100 g
Working Temperature
±0..+55
ø
C
Storage Temperature
-20..+70
ø
C
Vista de pagina 5