Register description
32 FM33xx
R37: Filter register
with the following possible entries:
The changes can only be made by way of the first channel, and are
adopted after a reset.
Entry – Conversion time – Suppression
0x0C 191 ms with 4.9 MHz 50 Hz filter
0x0D 160 ms with 4.9 MHz 60 Hz filter
0x0E 46 ms with 4.9 MHz 250 Hz filter
0x0F 30 ms with 4.9 MHz 500 Hz filter
R38: Back voltage reset time
Unit is seconds. Minimum value is 10 seconds. If an error occurs, another
attempt is made to activate the channel after the specified interval.
Measurement is then not carried out for one cycle.