Beckhoff CU2608 Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 22
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Mounting and cabling
CU2608 13
Power cable conductor losses
The ZK2020-xxxx-yyyy power cables should not exceed the total length of 15 m at 4 A (with continuation). When
planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer be assured if the
voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must also be taken into
account.
Example
8 m power cable with 0.34 mm² cross-section has a voltage drop of 3.2 V at 4 A.
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22

Comentarios a estos manuales

Sin comentarios