Data sheet for KL1002 and KL1012, Version 1.3
Beckhoff
®
and TwinCAT
®
are Beckhoff brands. Information is subject to change and are only binding if agreed contractually.
Beckhoff Automation GmbH, Eiserstr. 5, 33415 Verl, Germany, Tel.: +49 (0) 5246 963 0, Fax.: +49 (0) 5246 963 149, http://www.beckhoff.com
Two-channel, digital input terminals, 24 V
DC
The KL1002 and KL1012 digital input terminals acquire the binary control signals from the process level and transmit
them, in an electrically isolated form, to the higher-level automation unit. The KL1002 and KL1012 versions have input
filters of different speeds. The Bus Terminals contain two channels that indicate their signal state by means of light
emitting diodes.
Technical data KL1002/KS1002 KL1012/KS1012
Connection technology 4-wire
Number of inputs 2
Rated voltage 24 V
DC
(-15%/+20%)
Signal voltage “0” -3 V … +5 V
Signal voltage “1” +15 V … +30 V
Input filter 3 ms 0.2 ms
Input current typically 5 mA
Current consumption from K-bus typically 3 mA
Electrical isolation 500 V (K-Bus/field potential)
Bit width in process image 2 input bits
Configuration no address-or configuration settings required
Dimensions (W x H x D) 15mm x 100mm x 70mm (connected width: 12mm)
Weight approx. 50 g
during operation -25°C ... +60°C
0°C ... +55°C (according to cULus, for Canada and USA)
0°C ... +55°C (according to ATEX, see special conditions)
Permissible ambient
temperature range
during storage -40°C... +85°C
Relative humidity 5% ... 95%, no condensation
Vibration / shock resistance conforms to EN 60068-2-6 / EN 60068-2-27
EMC resistance/emission conforms to EN 61000-6-2 / EN 61000-6-4
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1

Data sheet for KL1002 and KL1012, Version 1.3 Beckhoff® and TwinCAT® are Beckhoff brands. Information is subject to change and are only binding if

Pagina 2 - WARNING

Data sheet for KL1002 and KL1012, Version 1.3 Beckhoff® and TwinCAT® are Beckhoff brands. Information is subject to change and are only binding if

Modelos relacionados KL1012

Comentarios a estos manuales

Sin comentarios