Beckhoff CX51x0 Manual de usuario Pagina 24

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 87
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 23
SecondsUPS
3.2.2 FUNCTION_BLOCKFB_NT_QuickShutdown
ThefunctionblockFB_NT_QuickShutdowncanbeusedtotriggeranimmediatereboot,withoutstopping
TwinCATortheWindowsoperatingsystem.
Attention:
Attention
Lossofdata
ThefunctionblockFB_NT_QuickShutdownisusedinternallybyFB_S_UPS_CX51x0.It
mustnotbeusedindependently,becausethiscouldresultindataloss!
FUNCTION_BLOCKFB_NT_QuickShutdown
VAR_INPUT
VAR_INPUT
NETID:T_AmsNetId;
START:BOOL;
TMOUT:TIME:=DEFAULT_ADS_TIMEOUT;
END_VAR
NETID:AmsNetIDofthecontroller.
START:Risingedgeleadstoimmediaterebootofthecontrolsystem.
TMOUT:Timeoutperiod.
VAR_OUTPUT
VAR_OUTPUT
BUSY:BOOL;
ERR:BOOL;
ERRID:UDINT;
END_VAR
BUSY:QuickShutdownisexecuted.
ERR:BecomesTRUE,assoonasanerroroccurs.
ERRID:SuppliestheerrornumberwhentheERRoutputisset.
Prerequisites
Developmentenvironment Targetplat
form
Hardware PLClibrariestoinclude
TwinCATv2.11R3Build2047orhigher
TwinCAT3.1Build4018orhigher
PC(i386) OnesecondUPS TcSUPS_CX51x0.Lib
CX51x024 Version1.0
Vista de pagina 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 86 87

Comentarios a estos manuales

Sin comentarios