Errorhandlinganddiagnostics
5 Errorhandlinganddiagnostics
5.1 BasicCPUmodule
5.1.1 LEDsonthebasicCPUmodule
Display LED Meaning
PWR PowersupplyThePowerLEDcomesonwhenthedeviceisconnectedto
alivepowersupplyunit(green).
TC TwinCATstatusLEDTwinCATisinRunmode(green)
TwinCATisinStopmode(red)
TwinCATisinConfigmode(blue)
HDD Read/WriteCompactFlash(red)IndicatesaccesstotheCFastcard.
FB1 StatusLED1forfieldbus(functioniswrittenatthefieldbusinterface)
FB2 StatusLED2forfieldbus(functioniswrittenatthefieldbusinterface)
5.1.2 LEDsofthepowersupplyunit(CX21000xx4)inKbusmode
Afterswitchingon,thepowersupplyimmediatelycheckstheconnectedBusTerminalconfiguration.IfKbus
terminalsaredetected,theerrorfreebootupissignaledbythered“I/OERRLED”goingout.Ifthe“I/OERR”
LEDblinks,anerrorintheareaoftheterminalsisindicated.Theerrorcodecanbedeterminedfromthe
frequencyandnumberofblinks.Thispermitsrapidrectificationoftheerror.
Display LED Meaning
Us24V PowersupplyfortheCPUmodule.TheLEDlights
greenifthepowersupplyiscorrect.
Up24V Powersupplyforterminalbus.TheLEDlightsgreenif
thepowersupplyiscorrect.
KBUS
RUN
Kbusdiagnostics.ThegreenLEDlightsupinorderto
indicatefaultfreeoperation."Faultfree"meansthat
thecommunicationwiththefieldbussystemisalso
running.
KBUS
ERR
Kbusdiagnostics.TheredLEDflashestoindicatean
error.TheredLEDblinkswithtwodifferent
frequencies.
Table9:TheI/OerrorLEDblinkcode
fastblinking Startoftheerrorcode
Firstslowsequence Errorcode
Secondslowsequence Errorcodeargument